Home » Steroglass » Cosmetics Laboratory » Thermo chiller S100 +5/+35°C HRSH150
Thermo chiller HRSH150 is designed to meet the thermostating needs of medium-sized instruments, and is best used in conjunction with rotary evaporators and coolers for reactors or distillation.
Thanks to the presence of three inverters that control the rotation speed of the compressor, fan, and pump motor, electrical consumption is reduced by up to 53%.
The HRSH series precisely monitors and controls the cooling system, allowing you to focus on other tasks. Use this smart solution to enable proactive control. Anticipate any changes through remote control and manage anomalies and issues in the cooling system. Improve the performance and reliability of your machine with exceptional temperature stability. Through simultaneous control of the compressor and fan of the DC inverter, and the electronic expansion valve, the temperature is kept stable at ±0.1 °C even when the thermal load varies significantly.
The use of an immersion pump without mechanical sealing means that the pump is not subject to any external leakage of the circulating fluid. Therefore, there is no need for regular checks for leaks or replacement of mechanical sealing. It is not necessary to drain the circulating fluid when removing the pump.
Due to the three inverters that control the speed of the compressor, fan, and pump, electrical consumption is reduced by up to 53%. The HRSH series monitors and controls the cooling system accurately, allowing you to focus on other tasks. Utilize a smart solution that provides proactive control. Predict potential changes via remote control and address issues in the cooling system. Improve the performance and reliability of your machine with superior temperature stability.
Through simultaneous control of the compressor and fan with a DC inverter, and the electronic expansion valve, temperature stability of ±0.1 °C is maintained even when the thermal load fluctuates significantly. The use of an immersion pump without a mechanical seal means the pump is not subject to any external leaks of the circulating fluid. Therefore, there is no need for periodic checks for pump leaks or replacement of the mechanical seal. It is also not necessary to drain the circulating fluid when removing the pump.
Condensation of solvents in Strike 100 rotary evaporators
Condensation of vapors in Pilot Reactor
Condensation of vapors in distillation equipment
Laser processing machines
Laser welding machines
Laser cutting machines
Cleaning machines
Printing machines
Injection molding machines
Arc welding machines
Resistance welding machines (spot welding)
High frequency induction heating equipment
Cooling water available anytime, anywhere
Cooling method: Air cooling
Refrigerant: R410A (HFC)
Refrigerant charge: 2.1 Kg
Control system: PID control
Ambient temperature / humidity / altitude: Temperature: 5 to 45 ° C
Circulating fluid system:
Circulating fluid: Tap water, 15% ethylene glycol aqueous solution, deionized water
Operating temperature range: 5 to 35 ° C
Cooling capacity (50/60 Hz): KW 15.7
Heating capacity (50/60 Hz): KW 3.0
Temperature stability: ± 0.1° C
Nominal flow rate (50/60 Hz): 45 l/min (0.5 MPa)
Maximum flow rate (50/60 Hz): 130 l/min
Maximum lifting height (50/60 Hz): 50 m
Adjustable pressure range: 0.1 – 0.5 MPa
Maximum operating flow: 25 l/min
Tank capacity: 42 L
Circulating fluid inlet and outlet ports: G 1
Tank drain connection: G 3/4
Material in contact with the fluid:
Metal: Stainless steel, copper (heat exchanger brazing), brass (pump, Y-filter), carbon, SiC
Resin: PE, PVC, POM, PTFE, NBR, EPDM, FKMElectric system:
Power supply: Three-phase 380-415 V AC (50/60 Hz)
Permissible voltage range: ±10% (Without DC voltage fluctuation)
Applicable earth leakage breaker:
Rated current: 30 A
Sensitivity of leakage current: 30 mA
Rated operating current: 9.3 A
Electric absorption: 5.8 kW (6.4 kVA)
Noise level (front 1 m / height 1 m): 68 dB (A)
Waterproof specification: IPX4
Dimensions (LxWxH): 954x715x1420 mm
Weight: 215 kg